How do I get the temp-4 sound to activate when a CO alarm occurs?

The temp-4 tone (built-in to the APB200 & APB200-LF Intelligent Sounder bases) is emitted during the activation of a CO operation within the MIX-COSAP device.

The CO alarm Input Zone must contain the ‘CO’ flag (F4 column within the MGC Configurator) to drive the temp-4 tone.